Municipal Lift Station with Building for New Residential Subdivision

Wastewater Lift StationRomtec DrawingRomtec Drawing
PROJECT DETAILS

The rural community of Scio is in the heart of Oregon’s Willamette Valley. A new 77-lot residential subdivision was planned on flat land about a mile from the municipal wastewater treatment plant. The subdivision’s sewer terminated approximately 30′ below the nearest gravity sewer, thus requiring a sewage lift station.

Romtec Utilities worked with the developer’s consulting civil engineer to design a complete sewer pumping system on a 1,850 sq. ft. site. The custom package wastewater pump station includes a Romtec building to house the lift station controls, sewage odor-control equipment and the pump station’s standby electrical generator. The duty point of the duplex submersible pumps is 191 GPM @ 69′ TDH.

THIS ROMTEC UTILITIES SYSTEM INCLUDED

  • City specified: Multitrode MT2PC controller, SCADA system, auxiliary power & hydrogen sulfide control system
  • Precast concrete wet well: 6’ dia. x 19’ deep, fall & confined space entry control, pedestrian-rated hatch
  • Pump disconnect panel: with free-air stand, cable hatch
  • Davit crane: Thern 5124 crane w/hand winch for lifting submersible pumps
  • Piping & accessories: all stainless steel
  • ITT Flygt submersible pumps: Two NP3127 HT, 10 HP solids-handling pumps
  • Fluid Level monitoring & control: Primary – MultiTrode probe, Redundant/Back-up – MultiTrode probe w/MTR relays
  • Precast concrete valve vault: Pedestrian-rated hatch, 4″ system, check & plug valves, discharge pressure gauge
  • Lift Station Standby Generator: Cummins 42 kW w/ATS, natural gas fuel
  • Control Building: Romtec 12′-8″ X 16′-8″ split-face concrete building
  • Sewer Pump Station Control Panel: UL listed
  • Pump station telemetry: Cellular SCADA and alarming system
  • Hydrogen sulfide/odor control: Air injection system

PDF with ADDITIONAL DETAILS

PDF with DRAWING

wastewater PREV bottom.jpg wastewater NEXTbottom.jpg

Services included with every Romtec Utilities Pump/Lift Station

Free pump/lift station sizing, pump performance curve, design proposal, quotation
All pump/lift station engineering – structural, mechanical, electrical – coordination with site engineer(s)
Pumping system submittals – CAD drawings, design and materials specifications
Sewer/water regulatory agency coordination and submittal approval assistance
Factory assembly of complete pre-packaged lift stations (prefabricated pumping systems)
Coordinated delivery of complete pump station to project site
On-site construction advisor and pump station start-up services
Operation and Maintenance (O&M) manuals